_AlertIE

TDK-Lambda Genesys 1U 1.5kW

Alimentation DC programmable rack 1U, 1500W, jusque 600V et 200A, entrée monophasé

TDK-Lambda
Code Testoon : TDKGen1U1500W
Série : Genesys 1U
Marque : TDK-Lambda
Alimentation DC programmable au format 1U.
Puissance: 1500W.
Tension: jusqu'à 0-600 V DC (selon modèle).
Courant: jusqu'à 0-200 A DC (selon modèle).
Entrée monophasé.
Interfaces RS-232 et RS-485 en standard.
Interfaces de communication et de programmation (Optionnelles): GPIB (compatible SCPI, programmation et interface maître pour le montage multi appareils), LAN (compatible LXI), USB, analogique isolée (programmation tension (0-5V & 0-10V) ou courant (4-20mA)), RS-485 esclave pour montage multi appareils. 

Produit à configuration (gamme de courant et tension, et interfaces de communication/programmation), nous consulter.
TTC HT
Quantité
Devis EXPRESS pour cet article
Devis EXPRESS pour cet article
Description

Genesys™ 1U series

 
Programmable 1U Rack Mount power supply

Genesys 1 U 1500 W Range
  Models    Gen8-180    Gen12.5-120    Gen20-76    Gen30-50    Gen40-38    Gen50-30    Gen60-25    Gen80-19    Gen100-15    Gen150-10    Gen300-5    Gen600-2.6  
Power
(W)
1440 W1500 W1520 W1500 W1520 W1500 W1520 W1500 W1560 W
Voltage
(V DC)
0-8 V0-12.5 V0-20 V0-30 V0-40 V0-50 V0-60 V0-80 V0-100 V0-150 V0-300 V0-600 V
Current
(A DC)
0-180 A0-120 A0-76 A0-50 A0-38 A0-30 A0-25 A0-19 A0-15 A0-10 A0-5 A0-2.6 A

  • High Power Density: 1500W in 1U
  • Wide Range Input (85 - 265Vac Continuous. single phase. 47/63Hz)
  • Active Power Factor Correction (0.99 typical)
  • Output Voltage up to 600V. Current up to 200A
  • Built-in RS-232/RS-485 Interface Standard
  • Last-Setting Memory
  • Front Panel Lock selectable from Front Panel or Software
  • High Resolution 16 bit ADCs & DACs
  • Reliable Encoders for Voltage and Current Adjustment
  • Constant Voltage/Constant Current auto-crossover
  • Advanced Parallel reports total current up to four identical units
  • Global Commands for Serial RS-232/RS-485 Interface
  • Independent Remote ON/OFF and Remote Enable/Disable
  • External Analog Programming and Monitoring (user selectable 0-5V & 0-10V)
  • Reliable Modular and SMT Design
  • 19" Rack Mounted ATE and OEM applications
  • Optional Interfaces
          Isolated Analog Programming and Monitoring Interface (0-5V/0-10V & 4-20mA)
          IEEE 488.2 SCPI (GPIB) Multi-Drop
          LXI Compliant LAN
  • LabView® and LabWindows® drivers
  • Five Year Warranty
          Worldwide Safety Agency Approvals; CE Mark for LVD and EMC Regulation

Applications
Genesys™ power supplies have been designed to meet the demands of a wide variety of applications.

Test and Measurement
Last-Setting memory simplifies test design and requires no battery backup.
Built-in RS-232/RS-485 gives maximum system flexibility along with 0-5V and 0-10V. selectable analog programming.
Wide range of available inputs allows testing of many different devices.

Semiconductor Burn-in
Safe-Start may be ENABLED to re-start at Output OFF to protect load.
Wide range input (85-265Vac) with Active Power Factor correction rides through input transients easily.

Component Test
High power density. zero stacking and single wire parallel operation give maximum system flexibility.

Laser Diode
OVP is directly set on Voltage Display. assuring accurate protection settings.
Current Limit Fold Back assures load is protected from current surges.

Heater Supplies
Smooth. reliable encoders enhance front panel control.
Remote analog programming is user selectable 0-5V or 0-10V.

RF Amplifiers and Magnets
Robust design assures stable operation under a wide variety of loads.
High linearity in voltage and current mode.

Spécifications
Garantie Constructeur Standard 5 Ans
755-Format - taille 1U
068-Puissance Max. 1500 W
057-Tension max. de sortie 600 V DC (selon modèle, voir les options)
058-Courant max. de sortie 200 A DC (selon modèle, voir les options)
056-Nombre de sorties Simple
717-Programmable Oui
501-Interfaces de programmation Analogique | RS-232 | USB | GPIB
055-Mode de fonctionnement (Type) Mode série | Mode parallèle | Mode maître/esclave
621-Ondulation et bruit 8 mV rms (ripple); 60 mV rms (noise)
En Stock Non
035-Dimensions (HxLxP) (mm) 43.6(1U)x482.6(Rack)x432.8 mm
013-Poids Net 8.5 kg
Fichiers à télécharger
Articles déjà vus